BE-t-2x280GC5-B01T C
311.07 kW
Defrost: None
Product code: BE-2x280AD1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 77,302 m³/h |
|---|---|
| External surface | 1,440.4 m² |
| Inner volume | 181.8 dm³ |
| Fin material | Aluminium |
| Net weight | 1,389 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x280AD1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 188.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 310.98 | 188.03 | not rated | not rated | not rated | not rated |
| 45 | 430.40 | 309.82 | 187.90 | not rated | not rated | not rated |
| 50 | 548.70 | 428.34 | 308.86 | 187.87 | not rated | not rated |
| 55 | 666.48 | 545.78 | 426.63 | 308.19 | 188.00 | not rated |
| 60 | 783.98 | 662.71 | 543.33 | 425.37 | 307.88 | 188.37 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 144.79 | not rated | not rated | not rated | not rated | not rated |
| 40 | 236.54 | 144.59 | not rated | not rated | not rated | not rated |
| 45 | 325.57 | 235.52 | 144.42 | not rated | not rated | not rated |
| 50 | 413.70 | 323.83 | 234.68 | 144.35 | not rated | not rated |
| 55 | 501.42 | 411.27 | 322.39 | 234.09 | 144.42 | not rated |
| 60 | 588.91 | 498.32 | 409.26 | 321.34 | 233.82 | 144.71 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 310.983 | 53.94 | 114.6 |
| Low speed (Y) | 236.536 | 41.02 | 70.6 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 2850 mm |
| F | 2230 mm |
| G | 3450 mm |
| E1 | 1250 mm |
| H | 3100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.