BE-t-2x291GB5-C04C C
309.97 kW
Defrost: None
Product code: BE-380FD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 66,211 m³/h |
|---|---|
| External surface | 2,677.6 m² |
| Inner volume | 471.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,663 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-380FD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 196.53 | not rated | not rated | not rated | not rated | not rated |
| 40 | 310.14 | 195.10 | not rated | not rated | not rated | not rated |
| 45 | 420.75 | 307.34 | 193.84 | not rated | not rated | not rated |
| 50 | 530.43 | 416.69 | 304.89 | 192.79 | not rated | not rated |
| 55 | 639.70 | 525.14 | 413.13 | 302.86 | 192.03 | not rated |
| 60 | 748.75 | 633.19 | 520.51 | 410.19 | 301.35 | 191.62 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 148.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 233.01 | 147.81 | not rated | not rated | not rated | not rated |
| 45 | 314.91 | 230.81 | 146.79 | not rated | not rated | not rated |
| 50 | 396.16 | 311.75 | 228.90 | 145.95 | not rated | not rated |
| 55 | 477.12 | 392.08 | 309.01 | 227.31 | 145.34 | not rated |
| 60 | 557.95 | 472.13 | 388.53 | 306.74 | 226.14 | 145.01 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 310.141 | 53.79 | 105.5 |
| Low speed (Y) | 233.014 | 40.41 | 63.5 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 7660 mm |
| F | 1050 mm |
| G | 8260 mm |
| E1 | 2430 mm |
| E2 | 2400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 8260 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.