Skip to Content

Dry cooler BE-2x280BB1-B01T C

Dry cooler BE-2x280BB1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280BB1-B01T C

Heat rejection i
244.64 kW
Air flow
84,562 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 84,562 m³/h
External surface 710.5 m²
Inner volume 109.3 dm³
Fin materialAluminium
Net weight 1,263 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x280BB1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
244.642 kW Fluid flow 42.46 m³/h Pressure drop 50.8 kPa
Heat rejection · Low speed (Y)
195.026 kW Fluid flow 33.85 m³/h Pressure drop 34.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 140.64 not rated not rated not rated not rated not rated
40 244.64 141.22 not rated not rated not rated not rated
45 346.23 244.52 141.73 not rated not rated not rated
50 447.04 345.49 244.42 142.19 not rated not rated
55 547.50 445.72 344.86 244.40 142.66 not rated
60 647.75 545.60 444.59 344.41 244.48 143.16

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 112.84 not rated not rated not rated not rated not rated
40 195.03 113.31 not rated not rated not rated not rated
45 275.02 194.83 113.68 not rated not rated not rated
50 354.33 274.28 194.66 114.03 not rated not rated
55 433.32 353.08 273.66 194.57 114.39 not rated
60 512.14 431.59 352.02 273.21 194.62 114.81

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 244.642 42.46 50.8
Low speed (Y) 195.026 33.85 34.0

Dimensions

Dimension drawing of BE-2x280BB1-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 2650 mm
F 2330 mm
G 3250 mm
E1 1150 mm
H 2900 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3250 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.