BE-291CC1-B04 C
245.35 kW
Defrost: None
Product code: BE-t-380GC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 61,847 m³/h |
|---|---|
| External surface | 657.1 m² |
| Inner volume | 100.6 dm³ |
| Fin material | Aluminium |
| Net weight | 809 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-380GC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 148.79 | not rated | not rated | not rated | not rated | not rated |
| 40 | 246.55 | 148.60 | not rated | not rated | not rated | not rated |
| 45 | 341.62 | 245.47 | 148.39 | not rated | not rated | not rated |
| 50 | 435.78 | 339.74 | 244.55 | 148.30 | not rated | not rated |
| 55 | 529.53 | 433.13 | 338.13 | 243.84 | 148.31 | not rated |
| 60 | 623.04 | 526.12 | 430.86 | 336.86 | 243.41 | 148.50 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 115.55 | not rated | not rated | not rated | not rated | not rated |
| 40 | 189.48 | 115.36 | not rated | not rated | not rated | not rated |
| 45 | 261.17 | 188.58 | 115.21 | not rated | not rated | not rated |
| 50 | 332.13 | 259.64 | 187.82 | 115.11 | not rated | not rated |
| 55 | 402.75 | 330.00 | 258.35 | 187.25 | 115.13 | not rated |
| 60 | 473.18 | 400.03 | 328.19 | 257.35 | 186.92 | 115.29 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 246.548 | 42.76 | 98.2 |
| Low speed (Y) | 189.478 | 32.86 | 61.6 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 3760 mm |
| F | 1050 mm |
| G | 4360 mm |
| E1 | 1130 mm |
| E2 | 1100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4360 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.