Dry cooler BE-291CD5-B04 C

Dry cooler BE-291CD5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-291CD5-B04 C

Heat rejection i
248.79 kW
Air flow
59,225 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 59,225 m³/h
External surface 1,591.9 m²
Inner volume 220.2 dm³
Fin materialAluminium
Net weight 1,050 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-291CD5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
248.792 kW Fluid flow 43.14 m³/h Pressure drop 45.7 kPa
Heat rejection · Low speed (Y)
193.835 kW Fluid flow 33.62 m³/h Pressure drop 29.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 151.80 not rated not rated not rated not rated not rated
40 248.79 151.30 not rated not rated not rated not rated
45 342.95 247.24 150.86 not rated not rated not rated
50 436.17 340.44 245.88 150.50 not rated not rated
55 528.96 432.74 338.24 244.76 150.27 not rated
60 621.52 524.63 429.73 336.42 243.94 150.23

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 119.40 not rated not rated not rated not rated not rated
40 193.84 118.95 not rated not rated not rated not rated
45 265.96 192.50 118.53 not rated not rated not rated
50 337.35 263.85 191.33 118.19 not rated not rated
55 408.39 334.49 262.00 190.36 117.97 not rated
60 479.24 404.80 331.99 260.48 189.67 117.92

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 248.792 43.14 45.7
Low speed (Y) 193.835 33.62 29.3

Dimensions

Dimension drawing of BE-291CD5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 5260 mm
F 1050 mm
G 5860 mm
E1 2430 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5860 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.