Skip to Content

Dry cooler BE-2x291BB5-C04C C

Dry cooler BE-2x291BB5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x291BB5-C04C C

Heat rejection i
252.00 kW
Air flow
108,993 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 108,993 m³/h
External surface 536.8 m²
Inner volume 94.9 dm³
Fin materialAluminium
Net weight 1,160 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x291BB5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
251.996 kW Fluid flow 43.74 m³/h Pressure drop 80.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
205.546 kW Fluid flow 35.67 m³/h Pressure drop 56.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 143.82 not rated not rated not rated not rated not rated
40 252.00 144.52 not rated not rated not rated not rated
45 358.14 252.17 145.12 not rated not rated not rated
50 463.65 357.87 252.35 145.67 not rated not rated
55 568.86 462.94 357.66 252.56 146.21 not rated
60 673.94 567.76 462.37 357.57 252.86 146.77

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 117.96 not rated not rated not rated not rated not rated
40 205.55 118.56 not rated not rated not rated not rated
45 291.30 205.71 119.09 not rated not rated not rated
50 376.49 291.10 205.87 119.57 not rated not rated
55 461.40 375.94 290.96 206.09 120.06 not rated
60 546.17 460.52 375.52 290.95 206.42 120.56

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 251.996 43.74 80.8
Low speed (Y) 205.546 35.67 56.3

Dimensions

Dimension drawing of BE-2x291BB5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 2850 mm
F 2230 mm
G 3450 mm
E1 1230 mm
H 3100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2850 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.