Skip to Content

Dry cooler BE-480BB1-B01 C

Dry cooler BE-480BB1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-480BB1-B01 C

Heat rejection i
253.11 kW
Air flow
85,567 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 85,567 m³/h
External surface 775.6 m²
Inner volume 100.6 dm³
Fin materialAluminium
Net weight 1,007 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-480BB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
253.114 kW Fluid flow 43.93 m³/h Pressure drop 42.8 kPa
Heat rejection · Low speed (Y)
201.602 kW Fluid flow 34.99 m³/h Pressure drop 28.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 145.64 not rated not rated not rated not rated not rated
40 253.11 146.23 not rated not rated not rated not rated
45 357.99 252.90 146.71 not rated not rated not rated
50 462.04 357.08 252.70 147.16 not rated not rated
55 565.70 460.48 356.29 252.59 147.61 not rated
60 669.16 563.51 459.13 355.70 252.62 148.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 116.77 not rated not rated not rated not rated not rated
40 201.60 117.22 not rated not rated not rated not rated
45 284.11 201.35 117.59 not rated not rated not rated
50 365.88 283.27 201.12 117.93 not rated not rated
55 447.32 364.49 282.54 200.98 118.29 not rated
60 528.57 445.39 363.28 281.98 200.96 118.69

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 253.114 43.93 42.8
Low speed (Y) 201.602 34.99 28.6

Dimensions

Dimension drawing of BE-480BB1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 4860 mm
F 1050 mm
G 5460 mm
E1 1130 mm
E2 1100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5460 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.