Dry cooler BE-391DB5-B04 C

Dry cooler BE-391DB5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-391DB5-B04 C

Heat rejection i
254.12 kW
Air flow
89,084 m³/h
Fans
3 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 3 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 89,084 m³/h
External surface 806.4 m²
Inner volume 117.7 dm³
Fin materialAluminium
Net weight 987 kg
Fans
Quantity 3
Diameter 910 mm
Speed 840 rpm
Power 8,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 95.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-391DB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
254.120 kW Fluid flow 44.11 m³/h Pressure drop 51.5 kPa
Heat rejection · Low speed (Y)
205.994 kW Fluid flow 35.75 m³/h Pressure drop 35.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 147.47 not rated not rated not rated not rated not rated
40 254.12 147.80 not rated not rated not rated not rated
45 358.39 253.71 148.08 not rated not rated not rated
50 461.89 357.32 253.34 148.34 not rated not rated
55 565.06 460.20 356.38 253.06 148.61 not rated
60 668.02 562.74 458.71 355.62 252.92 148.94

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 120.21 not rated not rated not rated not rated not rated
40 205.99 120.46 not rated not rated not rated not rated
45 289.67 205.57 120.65 not rated not rated not rated
50 372.65 288.66 205.19 120.82 not rated not rated
55 455.34 371.09 287.76 204.89 121.02 not rated
60 537.85 453.24 369.72 287.05 204.72 121.29

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 254.120 44.11 51.5
Low speed (Y) 205.994 35.75 35.5

Dimensions

Dimension drawing of BE-391DB5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 5860 mm
F 1050 mm
G 6460 mm
E1 1830 mm
E2 1800 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 6460 mm
Width 1210 mm
Height 1958 mm

Downloads