Skip to Content

Dry cooler BE-2x280DB5-B01C C

Dry cooler BE-2x280DB5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280DB5-B01C C

Heat rejection i
254.48 kW
Air flow
88,133 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 88,133 m³/h
External surface 831.3 m²
Inner volume 129.7 dm³
Fin materialAluminium
Net weight 1,340 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x280DB5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
254.481 kW Fluid flow 44.17 m³/h Pressure drop 52.2 kPa
Heat rejection · Low speed (Y)
203.771 kW Fluid flow 35.37 m³/h Pressure drop 35.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 147.81 not rated not rated not rated not rated not rated
40 254.48 148.15 not rated not rated not rated not rated
45 358.73 254.06 148.41 not rated not rated not rated
50 462.21 357.65 253.68 148.67 not rated not rated
55 565.35 460.50 356.69 253.39 148.94 not rated
60 668.29 563.01 458.99 355.92 253.26 149.27

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 119.06 not rated not rated not rated not rated not rated
40 203.77 119.30 not rated not rated not rated not rated
45 286.35 203.34 119.48 not rated not rated not rated
50 368.24 285.33 202.95 119.66 not rated not rated
55 449.84 366.69 284.44 202.65 119.87 not rated
60 531.26 447.74 365.32 283.74 202.50 120.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 254.481 44.17 52.2
Low speed (Y) 203.771 35.37 35.1

Dimensions

Dimension drawing of BE-2x280DB5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 4050 mm
F 2230 mm
G 4650 mm
E1 1850 mm
H 4300 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.