BE-2x280DB5-B01C C
254.48 kW
Defrost: None
Product code: BE-t-380HB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 66,708 m³/h |
|---|---|
| External surface | 806.4 m² |
| Inner volume | 117.7 dm³ |
| Fin material | Aluminium |
| Net weight | 972 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-380HB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 151.60 | not rated | not rated | not rated | not rated | not rated |
| 40 | 254.54 | 151.53 | not rated | not rated | not rated | not rated |
| 45 | 354.52 | 253.41 | 151.44 | not rated | not rated | not rated |
| 50 | 453.54 | 352.47 | 252.42 | 151.38 | not rated | not rated |
| 55 | 552.09 | 450.58 | 350.65 | 251.59 | 151.40 | not rated |
| 60 | 650.39 | 548.26 | 447.98 | 349.15 | 251.02 | 151.51 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 119.61 | not rated | not rated | not rated | not rated | not rated |
| 40 | 199.04 | 119.47 | not rated | not rated | not rated | not rated |
| 45 | 275.96 | 198.02 | 119.34 | not rated | not rated | not rated |
| 50 | 352.04 | 274.16 | 197.12 | 119.24 | not rated | not rated |
| 55 | 427.74 | 349.50 | 272.58 | 196.38 | 119.22 | not rated |
| 60 | 503.23 | 424.48 | 347.28 | 271.27 | 195.87 | 119.32 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 254.540 | 44.15 | 43.2 |
| Low speed (Y) | 199.043 | 34.52 | 27.9 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 5860 mm |
| F | 1050 mm |
| G | 6460 mm |
| E1 | 1830 mm |
| E2 | 1800 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 6460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.