Skip to Content

Dry cooler BE-t-2x280GB5-B01C C

Dry cooler BE-t-2x280GB5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x280GB5-B01C C

Heat rejection i
253.37 kW
Air flow
81,064 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 81,064 m³/h
External surface 508.0 m²
Inner volume 93.2 dm³
Fin materialAluminium
Net weight 1,106 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-t-2x280GB5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
253.371 kW Fluid flow 43.97 m³/h Pressure drop 59.0 kPa
Heat rejection · Low speed (Y)
200.610 kW Fluid flow 34.82 m³/h Pressure drop 39.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 146.35 not rated not rated not rated not rated not rated
40 253.37 146.94 not rated not rated not rated not rated
45 357.81 253.21 147.43 not rated not rated not rated
50 461.40 356.98 253.07 147.89 not rated not rated
55 564.60 459.95 356.28 253.03 148.38 not rated
60 667.58 562.53 458.72 355.80 253.16 148.95

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 116.90 not rated not rated not rated not rated not rated
40 200.61 117.35 not rated not rated not rated not rated
45 282.00 200.40 117.73 not rated not rated not rated
50 362.63 281.26 200.25 118.10 not rated not rated
55 442.93 361.36 280.61 200.20 118.50 not rated
60 523.03 441.16 360.32 280.21 200.31 118.97

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 253.371 43.97 59.0
Low speed (Y) 200.610 34.82 39.0

Dimensions

Dimension drawing of BE-t-2x280GB5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 2650 mm
F 2230 mm
G 3250 mm
E1 1150 mm
H 2900 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3250 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.