BE-580BC1-B01 C
365.81 kW
Defrost: None
Product code: BE-2x280CC1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 88,273 m³/h |
|---|---|
| External surface | 2,304.7 m² |
| Inner volume | 269.4 dm³ |
| Fin material | Aluminium |
| Net weight | 1,846 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x280CC1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 222.56 | not rated | not rated | not rated | not rated | not rated |
| 40 | 365.81 | 221.89 | not rated | not rated | not rated | not rated |
| 45 | 504.95 | 363.61 | 221.26 | not rated | not rated | not rated |
| 50 | 642.74 | 501.37 | 361.66 | 220.76 | not rated | not rated |
| 55 | 779.90 | 637.81 | 498.21 | 360.08 | 220.45 | not rated |
| 60 | 916.72 | 773.66 | 633.49 | 495.61 | 358.92 | 220.41 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 173.42 | not rated | not rated | not rated | not rated | not rated |
| 40 | 282.21 | 172.78 | not rated | not rated | not rated | not rated |
| 45 | 387.68 | 280.33 | 172.20 | not rated | not rated | not rated |
| 50 | 492.06 | 384.67 | 278.67 | 171.73 | not rated | not rated |
| 55 | 595.95 | 487.99 | 382.05 | 277.31 | 171.43 | not rated |
| 60 | 699.56 | 590.82 | 484.43 | 379.88 | 276.33 | 171.38 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 365.808 | 63.44 | 69.8 |
| Low speed (Y) | 282.214 | 48.95 | 43.9 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 5250 mm |
| F | 2230 mm |
| G | 5850 mm |
| E1 | 2450 mm |
| H | 5500 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.