Dry cooler BE-2x280CC5-B01T C

Dry cooler BE-2x280CC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280CC5-B01T C

Heat rejection i
359.09 kW
Air flow
89,502 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 89,502 m³/h
External surface 2,266.8 m²
Inner volume 327.4 dm³
Fin materialAluminium
Net weight 1,998 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2x280CC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
359.089 kW Fluid flow 62.28 m³/h Pressure drop 49.2 kPa
Heat rejection · Low speed (Y)
279.043 kW Fluid flow 48.39 m³/h Pressure drop 31.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 217.44 not rated not rated not rated not rated not rated
40 359.09 216.80 not rated not rated not rated not rated
45 496.84 357.03 216.24 not rated not rated not rated
50 633.29 493.45 355.21 215.81 not rated not rated
55 769.14 628.61 490.45 353.69 215.53 not rated
60 904.66 763.19 624.48 487.96 352.59 215.50

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 170.53 not rated not rated not rated not rated not rated
40 279.04 169.97 not rated not rated not rated not rated
45 384.35 277.25 169.44 not rated not rated not rated
50 488.59 381.46 275.67 169.01 not rated not rated
55 592.35 484.65 378.92 274.36 168.73 not rated
60 695.85 587.38 481.19 376.81 273.41 168.67

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 359.089 62.28 49.2
Low speed (Y) 279.043 48.39 31.4

Dimensions

Dimension drawing of BE-2x280CC5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 5250 mm
F 2330 mm
G 5850 mm
E1 2450 mm
H 5500 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5850 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.