BE-391FC5-B04 C
358.96 kW
Defrost: None
Product code: BE-2x280CC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 89,502 m³/h |
|---|---|
| External surface | 2,266.8 m² |
| Inner volume | 327.4 dm³ |
| Fin material | Aluminium |
| Net weight | 1,998 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x280CC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 217.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 359.09 | 216.80 | not rated | not rated | not rated | not rated |
| 45 | 496.84 | 357.03 | 216.24 | not rated | not rated | not rated |
| 50 | 633.29 | 493.45 | 355.21 | 215.81 | not rated | not rated |
| 55 | 769.14 | 628.61 | 490.45 | 353.69 | 215.53 | not rated |
| 60 | 904.66 | 763.19 | 624.48 | 487.96 | 352.59 | 215.50 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 170.53 | not rated | not rated | not rated | not rated | not rated |
| 40 | 279.04 | 169.97 | not rated | not rated | not rated | not rated |
| 45 | 384.35 | 277.25 | 169.44 | not rated | not rated | not rated |
| 50 | 488.59 | 381.46 | 275.67 | 169.01 | not rated | not rated |
| 55 | 592.35 | 484.65 | 378.92 | 274.36 | 168.73 | not rated |
| 60 | 695.85 | 587.38 | 481.19 | 376.81 | 273.41 | 168.67 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 359.089 | 62.28 | 49.2 |
| Low speed (Y) | 279.043 | 48.39 | 31.4 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 5250 mm |
| F | 2330 mm |
| G | 5850 mm |
| E1 | 2450 mm |
| H | 5500 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.