Skip to Content

Dry cooler BE-580AB1-B01 C

Dry cooler BE-580AB1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-580AB1-B01 C

Heat rejection i
360.10 kW
Air flow
107,759 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 107,759 m³/h
External surface 1,412.0 m²
Inner volume 171.5 dm³
Fin materialAluminium
Net weight 1,380 kg
Fans
Quantity 5
Diameter 800 mm
Speed 900 rpm
Power 9,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 87.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-580AB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
360.096 kW Fluid flow 62.49 m³/h Pressure drop 117.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
286.070 kW Fluid flow 49.65 m³/h Pressure drop 78.0 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 212.73 not rated not rated not rated not rated not rated
40 360.10 212.73 not rated not rated not rated not rated
45 504.11 359.02 212.71 not rated not rated not rated
50 647.00 501.99 358.05 212.73 not rated not rated
55 789.37 643.89 500.15 357.29 212.87 not rated
60 931.42 785.24 641.14 498.66 356.84 213.16

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 170.49 not rated not rated not rated not rated not rated
40 286.07 170.39 not rated not rated not rated not rated
45 398.72 285.03 170.30 not rated not rated not rated
50 510.46 396.82 284.08 170.26 not rated not rated
55 621.74 507.70 395.15 283.37 170.31 not rated
60 732.78 618.15 505.30 393.82 282.94 170.53

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 360.096 62.49 117.4
Low speed (Y) 286.070 49.65 78.0

Dimensions

Dimension drawing of BE-580AB1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 6460 mm
F 1050 mm
G 7060 mm
E1 1230 mm
E2 1200 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 7060 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.