Skip to Content

Dry cooler BE-2x291DB1-B04T C

Dry cooler BE-2x291DB1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x291DB1-B04T C

Heat rejection i
360.47 kW
Air flow
117,316 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 117,316 m³/h
External surface 1,162.7 m²
Inner volume 152.7 dm³
Fin materialAluminium
Net weight 1,548 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x291DB1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
360.465 kW Fluid flow 62.56 m³/h Pressure drop 75.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
290.233 kW Fluid flow 50.37 m³/h Pressure drop 51.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 210.19 not rated not rated not rated not rated not rated
40 360.47 210.57 not rated not rated not rated not rated
45 507.30 359.76 210.87 not rated not rated not rated
50 652.98 505.58 359.11 211.16 not rated not rated
55 798.18 650.31 504.07 358.61 211.49 not rated
60 943.06 794.58 648.00 502.86 358.35 211.96

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 170.34 not rated not rated not rated not rated not rated
40 290.23 170.60 not rated not rated not rated not rated
45 407.08 289.51 170.78 not rated not rated not rated
50 522.94 405.48 288.85 170.97 not rated not rated
55 638.34 520.52 404.09 288.35 171.20 not rated
60 753.46 635.08 518.41 402.97 288.07 171.56

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 360.465 62.56 75.1
Low speed (Y) 290.233 50.37 51.0

Dimensions

Dimension drawing of BE-2x291DB1-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 4050 mm
F 2330 mm
G 4650 mm
E1 1850 mm
H 4300 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4650 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.