Skip to Content

Dry cooler BE-2x280DD1-B01T C

Dry cooler BE-2x280DD1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280DD1-B01T C

Heat rejection i
360.92 kW
Air flow
86,569 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 86,569 m³/h
External surface 1,937.8 m²
Inner volume 227.1 dm³
Fin materialAluminium
Net weight 1,760 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x280DD1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
360.920 kW Fluid flow 62.59 m³/h Pressure drop 69.2 kPa
Heat rejection · Low speed (Y)
276.190 kW Fluid flow 47.91 m³/h Pressure drop 42.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 220.08 not rated not rated not rated not rated not rated
40 360.92 219.46 not rated not rated not rated not rated
45 497.64 358.80 218.88 not rated not rated not rated
50 633.03 494.19 356.94 218.44 not rated not rated
55 767.79 628.29 491.18 355.44 218.17 not rated
60 902.23 761.80 624.16 488.71 354.37 218.18

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 169.90 not rated not rated not rated not rated not rated
40 276.19 169.35 not rated not rated not rated not rated
45 379.15 274.43 168.85 not rated not rated not rated
50 481.04 376.33 272.89 168.45 not rated not rated
55 582.46 477.21 373.87 271.64 168.22 not rated
60 683.61 577.64 473.89 371.88 270.77 168.23

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 360.920 62.59 69.2
Low speed (Y) 276.190 47.91 42.9

Dimensions

Dimension drawing of BE-2x280DD1-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 4050 mm
F 2330 mm
G 4650 mm
E1 1850 mm
H 4300 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4650 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.