BE-t-2x380GC5-B01T C
476.22 kW
Defrost: None
Product code: BE-2x291CC1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 117,997 m³/h |
|---|---|
| External surface | 2,681.2 m² |
| Inner volume | 327.4 dm³ |
| Fin material | Aluminium |
| Net weight | 2,087 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x291CC1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 288.76 | not rated | not rated | not rated | not rated | not rated |
| 40 | 476.65 | 287.93 | not rated | not rated | not rated | not rated |
| 45 | 659.39 | 474.00 | 287.25 | not rated | not rated | not rated |
| 50 | 840.40 | 655.00 | 471.66 | 286.70 | not rated | not rated |
| 55 | 1020.61 | 834.33 | 651.14 | 469.74 | 286.38 | not rated |
| 60 | 1200.37 | 1012.88 | 829.00 | 647.97 | 468.39 | 286.41 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 228.58 | not rated | not rated | not rated | not rated | not rated |
| 40 | 373.81 | 227.84 | not rated | not rated | not rated | not rated |
| 45 | 514.73 | 371.47 | 227.16 | not rated | not rated | not rated |
| 50 | 654.24 | 510.97 | 369.43 | 226.62 | not rated | not rated |
| 55 | 793.10 | 649.09 | 507.67 | 367.76 | 226.28 | not rated |
| 60 | 931.60 | 786.60 | 644.60 | 504.96 | 366.56 | 226.25 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 476.651 | 82.67 | 81.5 |
| Low speed (Y) | 373.805 | 64.82 | 52.8 |
| A | 2880 mm |
|---|---|
| B | 2400 mm |
| C | 5250 mm |
| F | 2330 mm |
| G | 5850 mm |
| E1 | 2450 mm |
| H | 5500 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2880 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.