Skip to Content

Dry cooler BE-591EC5-B04 C

Dry cooler BE-591EC5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-591EC5-B04 C

Heat rejection i
476.11 kW
Air flow
135,243 m³/h
Fans
5 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 135,243 m³/h
External surface 1,514.1 m²
Inner volume 339.5 dm³
Fin materialAluminium
Net weight 1,549 kg
Fans
Quantity 5
Diameter 910 mm
Speed 840 rpm
Power 14,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BE-591EC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
476.109 kW Fluid flow 82.64 m³/h Pressure drop 89.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
373.725 kW Fluid flow 64.81 m³/h Pressure drop 58.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 283.20 not rated not rated not rated not rated not rated
40 476.11 283.20 not rated not rated not rated not rated
45 664.42 474.70 283.16 not rated not rated not rated
50 851.15 661.68 473.50 283.22 not rated not rated
55 1037.23 847.22 659.37 472.61 283.44 not rated
60 1222.95 1032.10 843.85 657.60 472.09 283.93

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 224.38 not rated not rated not rated not rated not rated
40 373.73 224.35 not rated not rated not rated not rated
45 519.28 372.61 224.35 not rated not rated not rated
50 663.54 517.15 371.68 224.44 not rated not rated
55 807.22 660.47 515.40 371.07 224.68 not rated
60 950.56 803.20 657.90 514.12 370.83 225.12

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 476.109 82.64 89.9
Low speed (Y) 373.725 64.81 58.4

Dimensions

Dimension drawing of BE-591EC5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 6460 mm
F 1050 mm
G 7060 mm
E1 1230 mm
E2 1200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 7060 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.