BE-t-480GC1-B01 C
349.23 kW
Defrost: None
Product code: BE-2x380AB5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 125,799 m³/h |
|---|---|
| External surface | 1,096.0 m² |
| Inner volume | 167.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,637 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x380AB5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 202.70 | not rated | not rated | not rated | not rated | not rated |
| 40 | 350.63 | 203.30 | not rated | not rated | not rated | not rated |
| 45 | 495.54 | 350.37 | 203.82 | not rated | not rated | not rated |
| 50 | 639.46 | 494.49 | 350.15 | 204.34 | not rated | not rated |
| 55 | 782.96 | 637.66 | 493.60 | 350.05 | 204.80 | not rated |
| 60 | 926.19 | 780.41 | 636.12 | 492.96 | 350.14 | 205.43 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 164.98 | not rated | not rated | not rated | not rated | not rated |
| 40 | 283.21 | 165.42 | not rated | not rated | not rated | not rated |
| 45 | 398.77 | 282.90 | 165.75 | not rated | not rated | not rated |
| 50 | 513.42 | 397.75 | 282.56 | 166.09 | not rated | not rated |
| 55 | 627.69 | 511.75 | 396.81 | 282.36 | 166.47 | not rated |
| 60 | 741.72 | 625.38 | 510.24 | 396.12 | 282.35 | 166.96 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 350.627 | 60.86 | 79.1 |
| Low speed (Y) | 283.211 | 49.15 | 54.0 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 4050 mm |
| F | 2230 mm |
| G | 4650 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| H | 4300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4650 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.