Skip to Content

Dry cooler BE-t-480GC1-B01 C

Dry cooler BE-t-480GC1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-480GC1-B01 C

Heat rejection i
349.23 kW
Air flow
81,442 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 81,442 m³/h
External surface 1,034.1 m²
Inner volume 125.7 dm³
Fin materialAluminium
Net weight 1,079 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-t-480GC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
349.227 kW Fluid flow 60.57 m³/h Pressure drop 111.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
264.034 kW Fluid flow 45.80 m³/h Pressure drop 67.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 213.37 not rated not rated not rated not rated not rated
40 349.23 212.90 not rated not rated not rated not rated
45 480.93 347.37 212.47 not rated not rated not rated
50 611.27 477.83 345.77 212.18 not rated not rated
55 740.97 606.99 475.18 344.53 212.09 not rated
60 870.33 735.54 603.33 473.10 343.76 212.30

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 163.24 not rated not rated not rated not rated not rated
40 264.03 162.81 not rated not rated not rated not rated
45 361.56 262.54 162.44 not rated not rated not rated
50 458.02 359.13 261.27 162.21 not rated not rated
55 554.01 454.71 357.07 260.31 162.14 not rated
60 649.73 549.83 451.91 355.49 259.74 162.33

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 349.227 60.57 111.0
Low speed (Y) 264.034 45.80 67.6

Dimensions

Dimension drawing of BE-t-480GC1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 4860 mm
F 1050 mm
G 5460 mm
E1 1130 mm
E2 1100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5460 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.