Skip to Content

Dry cooler BE-2x380BD5-B01C C

Dry cooler BE-2x380BD5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x380BD5-B01C C

Heat rejection i
404.19 kW
Air flow
116,283 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 116,283 m³/h
External surface 1,270.1 m²
Inner volume 191.7 dm³
Fin materialAluminium
Net weight 1,681 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2x380BD5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
404.193 kW Fluid flow 70.15 m³/h Pressure drop 95.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
312.452 kW Fluid flow 54.19 m³/h Pressure drop 60.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 240.03 not rated not rated not rated not rated not rated
40 404.19 240.29 not rated not rated not rated not rated
45 564.37 403.40 240.56 not rated not rated not rated
50 723.17 562.60 402.76 240.87 not rated not rated
55 881.42 720.50 561.13 402.40 241.31 not rated
60 1039.32 877.84 718.29 560.15 402.41 241.98

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 187.16 not rated not rated not rated not rated not rated
40 312.45 187.31 not rated not rated not rated not rated
45 434.40 311.69 187.45 not rated not rated not rated
50 555.26 432.84 311.08 187.67 not rated not rated
55 675.61 552.94 431.59 310.71 188.00 not rated
60 795.68 672.56 551.07 430.73 310.68 188.53

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 404.193 70.15 95.0
Low speed (Y) 312.452 54.19 60.1

Dimensions

Dimension drawing of BE-2x380BD5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 3750 mm
F 2230 mm
G 4350 mm
E1 1150 mm
E2 1100 mm
H 4000 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4350 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.