BE-2x380DB5-B01T C
404.01 kW
Defrost: None
Product code: BE-2x380BD5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 116,283 m³/h |
|---|---|
| External surface | 1,270.1 m² |
| Inner volume | 191.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,681 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x380BD5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 240.03 | not rated | not rated | not rated | not rated | not rated |
| 40 | 404.19 | 240.29 | not rated | not rated | not rated | not rated |
| 45 | 564.37 | 403.40 | 240.56 | not rated | not rated | not rated |
| 50 | 723.17 | 562.60 | 402.76 | 240.87 | not rated | not rated |
| 55 | 881.42 | 720.50 | 561.13 | 402.40 | 241.31 | not rated |
| 60 | 1039.32 | 877.84 | 718.29 | 560.15 | 402.41 | 241.98 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 187.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 312.45 | 187.31 | not rated | not rated | not rated | not rated |
| 45 | 434.40 | 311.69 | 187.45 | not rated | not rated | not rated |
| 50 | 555.26 | 432.84 | 311.08 | 187.67 | not rated | not rated |
| 55 | 675.61 | 552.94 | 431.59 | 310.71 | 188.00 | not rated |
| 60 | 795.68 | 672.56 | 551.07 | 430.73 | 310.68 | 188.53 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 404.193 | 70.15 | 95.0 |
| Low speed (Y) | 312.452 | 54.19 | 60.1 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 3750 mm |
| F | 2230 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.