BE-t-2x291HB5-B04T C
403.94 kW
Defrost: None
Product code: BE-2x380DB5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 133,748 m³/h |
|---|---|
| External surface | 1,477.4 m² |
| Inner volume | 222.9 dm³ |
| Fin material | Aluminium |
| Net weight | 2,083 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x380DB5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 235.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 404.01 | 235.80 | not rated | not rated | not rated | not rated |
| 45 | 568.66 | 403.16 | 236.14 | not rated | not rated | not rated |
| 50 | 732.04 | 566.69 | 402.40 | 236.46 | not rated | not rated |
| 55 | 894.82 | 728.96 | 564.92 | 401.79 | 236.82 | not rated |
| 60 | 1057.29 | 890.70 | 726.24 | 563.47 | 401.42 | 237.29 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 188.96 | not rated | not rated | not rated | not rated | not rated |
| 40 | 322.54 | 189.29 | not rated | not rated | not rated | not rated |
| 45 | 452.54 | 321.69 | 189.53 | not rated | not rated | not rated |
| 50 | 581.42 | 450.72 | 320.94 | 189.74 | not rated | not rated |
| 55 | 709.79 | 578.66 | 449.09 | 320.33 | 190.00 | not rated |
| 60 | 837.88 | 706.11 | 576.23 | 447.77 | 319.95 | 190.37 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 404.009 | 70.11 | 44.7 |
| Low speed (Y) | 322.538 | 55.98 | 29.9 |
| A | 2778 mm |
|---|---|
| B | 2400 mm |
| C | 5850 mm |
| F | 2330 mm |
| G | 6450 mm |
| E1 | 1850 mm |
| E2 | 1800 mm |
| H | 6100 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 6450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2778 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.