Skip to Content

Dry cooler BE-2x380DC5-B01C C

Dry cooler BE-2x380DC5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x380DC5-B01C C

Heat rejection i
441.59 kW
Air flow
130,205 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 3 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): C — C: container delivery version

Data

Coil
Air flow 130,205 m³/h
External surface 1,662.6 m²
Inner volume 236.0 dm³
Fin materialAluminium
Net weight 1,997 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2x380DC5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
441.589 kW Fluid flow 76.65 m³/h Pressure drop 44.0 kPa
Heat rejection · Low speed (Y)
347.441 kW Fluid flow 60.29 m³/h Pressure drop 28.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 259.57 not rated not rated not rated not rated not rated
40 441.59 259.94 not rated not rated not rated not rated
45 618.77 440.36 260.18 not rated not rated not rated
50 794.42 616.20 439.27 260.43 not rated not rated
55 969.31 790.50 613.93 438.43 260.78 not rated
60 1143.87 964.20 787.11 612.06 437.93 261.28

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 205.67 not rated not rated not rated not rated not rated
40 347.44 205.90 not rated not rated not rated not rated
45 484.99 346.30 206.06 not rated not rated not rated
50 621.26 482.73 345.28 206.22 not rated not rated
55 756.91 617.90 480.74 344.50 206.46 not rated
60 892.23 752.50 614.98 479.14 344.02 206.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 441.589 76.65 44.0
Low speed (Y) 347.441 60.29 28.6

Dimensions

Dimension drawing of BE-2x380DC5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 5850 mm
F 2230 mm
G 6450 mm
E1 1850 mm
E2 1800 mm
H 6100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.