Skip to Content

Dry cooler BE-2x480BB5-B01T C

Dry cooler BE-2x480BB5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480BB5-B01T C

Heat rejection i
444.43 kW
Air flow
170,644 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 170,644 m³/h
External surface 1,203.8 m²
Inner volume 230.7 dm³
Fin materialAluminium
Net weight 2,166 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480BB5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
444.429 kW Fluid flow 77.13 m³/h Pressure drop 38.9 kPa
Heat rejection · Low speed (Y)
357.609 kW Fluid flow 62.07 m³/h Pressure drop 26.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 253.83 not rated not rated not rated not rated not rated
40 444.43 255.08 not rated not rated not rated not rated
45 630.82 444.44 256.12 not rated not rated not rated
50 815.92 629.78 444.44 257.08 not rated not rated
55 1000.39 813.89 628.89 444.53 257.99 not rated
60 1184.54 997.42 812.15 628.28 444.83 258.95

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 205.38 not rated not rated not rated not rated not rated
40 357.61 206.37 not rated not rated not rated not rated
45 506.02 357.50 207.21 not rated not rated not rated
50 653.24 505.01 357.41 207.96 not rated not rated
55 799.93 651.40 504.15 357.42 208.71 not rated
60 946.31 797.27 649.82 503.54 357.60 209.50

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 444.429 77.13 38.9
Low speed (Y) 357.609 62.07 26.4

Dimensions

Dimension drawing of BE-2x480BB5-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 4850 mm
F 2330 mm
G 5450 mm
E1 1150 mm
E2 2200 mm
H 5100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5450 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.