Skip to Content

Dry cooler BE-2x391AB5-B04T C

Dry cooler BE-2x391AB5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x391AB5-B04T C

Heat rejection i
444.84 kW
Air flow
167,586 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 167,586 m³/h
External surface 1,275.1 m²
Inner volume 208.2 dm³
Fin materialAluminium
Net weight 1,867 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2x391AB5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
444.844 kW Fluid flow 77.20 m³/h Pressure drop 88.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
364.749 kW Fluid flow 63.30 m³/h Pressure drop 62.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 256.37 not rated not rated not rated not rated not rated
40 444.84 257.19 not rated not rated not rated not rated
45 629.65 444.60 257.89 not rated not rated not rated
50 813.29 628.44 444.44 258.56 not rated not rated
55 996.35 811.14 627.46 444.40 259.25 not rated
60 1179.12 993.29 809.34 626.77 444.59 260.04

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 211.69 not rated not rated not rated not rated not rated
40 364.75 212.29 not rated not rated not rated not rated
45 514.48 364.42 212.83 not rated not rated not rated
50 663.14 513.30 364.15 213.34 not rated not rated
55 811.29 661.16 512.32 364.03 213.88 not rated
60 959.17 808.52 659.48 511.65 364.15 214.54

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 444.844 77.20 88.6
Low speed (Y) 364.749 63.30 62.3

Dimensions

Dimension drawing of BE-2x391AB5-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 4050 mm
F 2330 mm
G 4650 mm
E1 1250 mm
E2 1200 mm
H 4300 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4650 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.