BE-880AB1-B01 C
553.70 kW
Defrost: None
Product code: BE-2x380FC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 133,177 m³/h |
|---|---|
| External surface | 3,233.3 m² |
| Inner volume | 733.9 dm³ |
| Fin material | Aluminium |
| Net weight | 2,947 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x380FC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 339.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 554.17 | 337.70 | not rated | not rated | not rated | not rated |
| 45 | 763.46 | 550.62 | 336.50 | not rated | not rated | not rated |
| 50 | 970.81 | 757.84 | 547.48 | 335.55 | not rated | not rated |
| 55 | 1177.28 | 963.18 | 752.89 | 544.90 | 334.89 | not rated |
| 60 | 1383.26 | 1167.67 | 956.48 | 748.79 | 543.00 | 334.67 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 263.45 | not rated | not rated | not rated | not rated | not rated |
| 40 | 426.67 | 262.27 | not rated | not rated | not rated | not rated |
| 45 | 585.25 | 423.68 | 261.21 | not rated | not rated | not rated |
| 50 | 742.30 | 580.59 | 421.03 | 260.34 | not rated | not rated |
| 55 | 898.66 | 736.04 | 576.50 | 418.86 | 259.75 | not rated |
| 60 | 1054.65 | 890.82 | 730.55 | 573.12 | 417.26 | 259.54 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 554.172 | 96.11 | 51.5 |
| Low speed (Y) | 426.667 | 73.99 | 32.4 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 7650 mm |
| F | 2330 mm |
| G | 8250 mm |
| E1 | 2450 mm |
| E2 | 2400 mm |
| H | 7900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 8250 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.