BE-2x380FC5-B01T C
554.17 kW
Defrost: None
Product code: BE-880AB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 172,415 m³/h |
|---|---|
| External surface | 2,259.2 m² |
| Inner volume | 292.0 dm³ |
| Fin material | Aluminium |
| Net weight | 2,172 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-880AB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 315.60 | not rated | not rated | not rated | not rated | not rated |
| 40 | 553.70 | 317.35 | not rated | not rated | not rated | not rated |
| 45 | 785.14 | 553.28 | 318.82 | not rated | not rated | not rated |
| 50 | 1014.46 | 782.89 | 552.87 | 320.09 | not rated | not rated |
| 55 | 1242.79 | 1010.52 | 780.94 | 552.64 | 321.33 | not rated |
| 60 | 1470.54 | 1237.16 | 1007.03 | 779.40 | 552.75 | 322.71 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 253.45 | not rated | not rated | not rated | not rated | not rated |
| 40 | 440.89 | 254.81 | not rated | not rated | not rated | not rated |
| 45 | 622.21 | 440.30 | 255.89 | not rated | not rated | not rated |
| 50 | 801.67 | 620.06 | 439.75 | 256.85 | not rated | not rated |
| 55 | 980.24 | 798.05 | 618.15 | 439.39 | 257.80 | not rated |
| 60 | 1158.28 | 975.19 | 794.89 | 616.69 | 439.27 | 258.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 553.702 | 96.11 | 21.3 |
| Low speed (Y) | 440.886 | 76.52 | 14.1 |
| A | 1808 mm |
|---|---|
| B | 1300 mm |
| C | 10060 mm |
| F | 1150 mm |
| G | 10660 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 10660 mm |
|---|---|
| Width | 1300 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.