Skip to Content

Dry cooler BE-2x391BC1-C04C C

Dry cooler BE-2x391BC1-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x391BC1-C04C C

Heat rejection i
486.09 kW
Air flow
154,903 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 154,903 m³/h
External surface 1,267.8 m²
Inner volume 167.3 dm³
Fin materialAluminium
Net weight 1,714 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.6 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2x391BC1-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
486.086 kW Fluid flow 84.37 m³/h Pressure drop 104.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
381.620 kW Fluid flow 66.23 m³/h Pressure drop 67.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 283.68 not rated not rated not rated not rated not rated
40 486.09 284.50 not rated not rated not rated not rated
45 683.84 485.70 285.23 not rated not rated not rated
50 880.08 682.37 485.43 285.96 not rated not rated
55 1075.64 877.60 681.20 485.39 286.81 not rated
60 1270.79 1072.13 875.56 680.47 485.69 287.80

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 224.58 not rated not rated not rated not rated not rated
40 381.62 225.23 not rated not rated not rated not rated
45 534.66 381.29 225.84 not rated not rated not rated
50 686.33 533.48 381.11 226.46 not rated not rated
55 837.47 684.35 532.55 381.13 227.21 not rated
60 988.24 834.70 682.82 532.08 381.51 228.11

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 486.086 84.37 104.3
Low speed (Y) 381.620 66.23 67.9

Dimensions

Dimension drawing of BE-2x391BC1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 4050 mm
F 2230 mm
G 4650 mm
E1 1230 mm
E2 1200 mm
H 4300 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4050 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.