Product code: BE-780EB5-B01 C

Heat rejection i
486.69 kW
Air flow
149,637 m³/h
Fans
7 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 7 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 149,637 m³/h
External surface 1,589.8 m²
Inner volume 354.7 dm³
Fin materialAluminium
Net weight 1,920 kg
Fans
Quantity 7
Diameter 800 mm
Speed 900 rpm
Power 12,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.5 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-780EB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
486.691 kW Fluid flow 84.46 m³/h Pressure drop 96.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
385.565 kW Fluid flow 66.92 m³/h Pressure drop 63.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 287.91 not rated not rated not rated not rated not rated
40 486.69 287.88 not rated not rated not rated not rated
45 681.10 485.27 287.82 not rated not rated not rated
50 874.09 678.42 484.06 287.82 not rated not rated
55 1066.42 870.13 676.07 483.09 287.96 not rated
60 1258.36 1061.23 866.71 674.19 482.51 288.32

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 229.92 not rated not rated not rated not rated not rated
40 385.57 229.80 not rated not rated not rated not rated
45 537.50 384.26 229.66 not rated not rated not rated
50 688.16 535.07 383.12 229.59 not rated not rated
55 838.31 684.73 533.00 382.24 229.68 not rated
60 988.16 833.86 681.76 531.36 381.68 229.95

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 486.691 84.46 96.5
Low speed (Y) 385.565 66.92 63.8

Dimensions

Dimension drawing of BE-780EB5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 8860 mm
F 1050 mm
G 9460 mm
E1 1230 mm
E2 1200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 9460 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.