BE-980AB1-B01 C
628.70 kW
Defrost: None
Product code: BE-2x480AD5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 163,139 m³/h |
|---|---|
| External surface | 2,833.5 m² |
| Inner volume | 433.9 dm³ |
| Fin material | Aluminium |
| Net weight | 2,708 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x480AD5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 378.56 | not rated | not rated | not rated | not rated | not rated |
| 40 | 629.13 | 378.18 | not rated | not rated | not rated | not rated |
| 45 | 873.21 | 626.66 | 377.85 | not rated | not rated | not rated |
| 50 | 1115.09 | 868.84 | 624.57 | 377.66 | not rated | not rated |
| 55 | 1355.96 | 1108.88 | 865.10 | 622.97 | 377.69 | not rated |
| 60 | 1596.27 | 1347.94 | 1103.57 | 862.20 | 622.05 | 378.20 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 294.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 485.07 | 294.47 | not rated | not rated | not rated | not rated |
| 45 | 669.83 | 482.99 | 294.14 | not rated | not rated | not rated |
| 50 | 852.80 | 666.24 | 481.24 | 293.97 | not rated | not rated |
| 55 | 1034.94 | 847.77 | 663.23 | 479.95 | 294.08 | not rated |
| 60 | 1216.63 | 1028.50 | 843.53 | 660.94 | 479.28 | 294.54 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 629.133 | 109.11 | 83.9 |
| Low speed (Y) | 485.068 | 84.12 | 52.9 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 5250 mm |
| F | 2330 mm |
| G | 5850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 5500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.