Skip to Content

Dry cooler BE-2x491AC5-C04C C

Dry cooler BE-2x491AC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x491AC5-C04C C

Heat rejection i
627.60 kW
Air flow
207,656 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 207,656 m³/h
External surface 1,868.4 m²
Inner volume 301.9 dm³
Fin materialAluminium
Net weight 2,289 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x491AC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
627.602 kW Fluid flow 108.92 m³/h Pressure drop 79.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
499.951 kW Fluid flow 86.76 m³/h Pressure drop 53.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 364.47 not rated not rated not rated not rated not rated
40 627.60 365.65 not rated not rated not rated not rated
45 884.98 627.24 366.67 not rated not rated not rated
50 1140.49 883.25 627.04 367.67 not rated not rated
55 1395.11 1137.45 881.91 627.07 368.76 not rated
60 1649.28 1390.82 1134.97 881.04 627.50 370.05

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 292.99 not rated not rated not rated not rated not rated
40 499.95 293.91 not rated not rated not rated not rated
45 701.85 499.61 294.72 not rated not rated not rated
50 902.06 700.37 499.39 295.55 not rated not rated
55 1101.52 899.55 699.26 499.45 296.50 not rated
60 1300.48 1097.91 897.49 698.65 499.93 297.69

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 627.602 108.92 79.6
Low speed (Y) 499.951 86.76 53.2

Dimensions

Dimension drawing of BE-2x491AC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 5250 mm
F 2230 mm
G 5850 mm
E1 1250 mm
E2 2400 mm
H 5500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5250 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.