BE-791ED5-B04 C
717.88 kW
Defrost: None
Product code: BE-2x480CC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 179,004 m³/h |
|---|---|
| External surface | 4,533.6 m² |
| Inner volume | 638.2 dm³ |
| Fin material | Aluminium |
| Net weight | 3,659 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x480CC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 434.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 717.97 | 433.38 | not rated | not rated | not rated | not rated |
| 45 | 993.48 | 713.87 | 432.28 | not rated | not rated | not rated |
| 50 | 1266.39 | 986.71 | 710.23 | 431.43 | not rated | not rated |
| 55 | 1538.10 | 1257.04 | 980.73 | 707.21 | 430.87 | not rated |
| 60 | 1809.15 | 1526.21 | 1248.80 | 975.76 | 705.01 | 430.83 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 340.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 557.94 | 339.77 | not rated | not rated | not rated | not rated |
| 45 | 768.56 | 554.37 | 338.73 | not rated | not rated | not rated |
| 50 | 977.06 | 762.80 | 551.22 | 337.88 | not rated | not rated |
| 55 | 1184.59 | 969.19 | 757.72 | 548.60 | 337.33 | not rated |
| 60 | 1391.58 | 1174.65 | 962.27 | 753.51 | 546.69 | 337.22 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 717.970 | 124.52 | 49.4 |
| Low speed (Y) | 557.941 | 96.75 | 31.5 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 10050 mm |
| F | 2330 mm |
| G | 10650 mm |
| E1 | 2450 mm |
| E2 | 4800 mm |
| H | 10300 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 10650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.