Skip to Content

Dry cooler BE-2x680BB1-B01T C

Dry cooler BE-2x680BB1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x680BB1-B01T C

Heat rejection i
716.75 kW
Air flow
253,686 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 253,686 m³/h
External surface 2,131.6 m²
Inner volume 298.8 dm³
Fin materialAluminium
Net weight 3,324 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x680BB1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
716.754 kW Fluid flow 124.39 m³/h Pressure drop 25.5 kPa
Heat rejection · Low speed (Y)
571.874 kW Fluid flow 99.25 m³/h Pressure drop 16.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 402.59 not rated not rated not rated not rated not rated
40 716.75 405.93 not rated not rated not rated not rated
45 1022.37 717.50 408.72 not rated not rated not rated
50 1325.28 1021.03 718.09 411.19 not rated not rated
55 1627.05 1322.07 1019.89 718.78 413.39 not rated
60 1928.11 1622.05 1319.38 1019.18 719.68 415.61

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 322.90 not rated not rated not rated not rated not rated
40 571.87 325.66 not rated not rated not rated not rated
45 812.78 572.16 327.92 not rated not rated not rated
50 1051.18 811.26 572.43 329.89 not rated not rated
55 1288.53 1048.08 809.98 572.79 331.76 not rated
60 1525.23 1283.85 1045.42 809.12 573.43 333.63

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 716.754 124.39 25.5
Low speed (Y) 571.874 99.25 16.9

Dimensions

Dimension drawing of BE-2x680BB1-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 7050 mm
F 2330 mm
G 7650 mm
E1 1150 mm
E2 1100 mm
E3 2200 mm
H 7300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.