BE-2x680BB1-B01T C
716.75 kW
Defrost: None
Product code: BE-2x580EB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 207,997 m³/h |
|---|---|
| External surface | 2,385.6 m² |
| Inner volume | 493.7 dm³ |
| Fin material | Aluminium |
| Net weight | 2,983 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x580EB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 425.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 716.59 | 425.14 | not rated | not rated | not rated | not rated |
| 45 | 1001.27 | 714.52 | 425.12 | not rated | not rated | not rated |
| 50 | 1283.63 | 997.28 | 712.77 | 425.26 | not rated | not rated |
| 55 | 1565.02 | 1277.77 | 993.78 | 711.48 | 425.60 | not rated |
| 60 | 1845.86 | 1557.34 | 1272.77 | 991.17 | 710.78 | 426.30 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 336.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 561.99 | 336.37 | not rated | not rated | not rated | not rated |
| 45 | 781.88 | 560.16 | 336.27 | not rated | not rated | not rated |
| 50 | 999.87 | 778.49 | 558.64 | 336.32 | not rated | not rated |
| 55 | 1216.99 | 994.97 | 775.63 | 557.53 | 336.57 | not rated |
| 60 | 1433.63 | 1210.60 | 990.85 | 773.49 | 557.02 | 337.17 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 716.588 | 124.37 | 110.2 |
| Low speed (Y) | 561.990 | 97.47 | 71.6 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 6450 mm |
| F | 2330 mm |
| G | 7050 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7050 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.