BE-980AD5-B01 C
741.51 kW
Defrost: None
Product code: BE-2x480CD5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 175,586 m³/h |
|---|---|
| External surface | 4,871.1 m² |
| Inner volume | 665.9 dm³ |
| Fin material | Aluminium |
| Net weight | 3,578 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x480CD5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 452.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 741.10 | 451.02 | not rated | not rated | not rated | not rated |
| 45 | 1021.20 | 736.49 | 449.71 | not rated | not rated | not rated |
| 50 | 1298.50 | 1013.73 | 732.44 | 448.64 | not rated | not rated |
| 55 | 1574.51 | 1288.28 | 1007.18 | 729.09 | 447.97 | not rated |
| 60 | 1849.81 | 1561.59 | 1279.33 | 1001.77 | 726.69 | 447.88 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 351.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 569.13 | 349.67 | not rated | not rated | not rated | not rated |
| 45 | 780.44 | 565.23 | 348.46 | not rated | not rated | not rated |
| 50 | 989.55 | 774.26 | 561.80 | 347.48 | not rated | not rated |
| 55 | 1197.65 | 981.19 | 768.86 | 558.99 | 346.87 | not rated |
| 60 | 1405.20 | 1187.16 | 973.90 | 764.43 | 556.99 | 346.75 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 741.102 | 128.52 | 47.0 |
| Low speed (Y) | 569.131 | 98.72 | 29.3 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 10050 mm |
| F | 2230 mm |
| G | 10650 mm |
| E1 | 2450 mm |
| E2 | 4800 mm |
| H | 10300 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 10650 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.