Skip to Content

Dry cooler BE-2x480FB1-B01C C

Dry cooler BE-2x480FB1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480FB1-B01C C

Heat rejection i
686.08 kW
Air flow
177,022 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 177,022 m³/h
External surface 3,280.8 m²
Inner volume 631.2 dm³
Fin materialAluminium
Net weight 3,172 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480FB1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
686.082 kW Fluid flow 118.98 m³/h Pressure drop 95.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
534.076 kW Fluid flow 92.62 m³/h Pressure drop 61.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 414.97 not rated not rated not rated not rated not rated
40 686.08 413.77 not rated not rated not rated not rated
45 950.47 682.41 412.70 not rated not rated not rated
50 1212.57 944.47 679.19 411.86 not rated not rated
55 1473.63 1204.30 939.19 676.52 411.22 not rated
60 1734.10 1463.11 1197.03 934.82 674.60 411.17

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 325.83 not rated not rated not rated not rated not rated
40 534.08 324.71 not rated not rated not rated not rated
45 736.72 530.88 323.70 not rated not rated not rated
50 937.52 731.61 528.07 322.88 not rated not rated
55 1137.47 930.55 727.14 525.77 322.37 not rated
60 1336.95 1128.67 924.45 723.45 524.13 322.26

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 686.082 118.98 95.4
Low speed (Y) 534.076 92.62 61.2

Dimensions

Dimension drawing of BE-2x480FB1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.