Skip to Content

Dry cooler BE-t-2x391HC1-C04C C

Dry cooler BE-t-2x391HC1-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x391HC1-C04C C

Heat rejection i
686.20 kW
Air flow
164,780 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 164,780 m³/h
External surface 1,902.3 m²
Inner volume 261.7 dm³
Fin materialAluminium
Net weight 2,073 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 98.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-t-2x391HC1-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
686.195 kW Fluid flow 119.00 m³/h Pressure drop 73.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
529.217 kW Fluid flow 91.79 m³/h Pressure drop 46.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 413.98 not rated not rated not rated not rated not rated
40 686.20 413.58 not rated not rated not rated not rated
45 949.79 682.94 413.18 not rated not rated not rated
50 1210.49 944.00 680.13 412.98 not rated not rated
55 1469.85 1202.29 939.01 677.93 413.08 not rated
60 1728.45 1459.30 1195.23 935.04 676.55 413.66

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 322.91 not rated not rated not rated not rated not rated
40 529.22 322.49 not rated not rated not rated not rated
45 728.41 526.52 322.09 not rated not rated not rated
50 925.28 723.76 524.19 321.88 not rated not rated
55 1121.07 918.78 719.76 522.41 321.95 not rated
60 1316.27 1112.78 913.20 716.63 521.34 322.45

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 686.195 119.00 73.0
Low speed (Y) 529.217 91.79 46.0

Dimensions

Dimension drawing of BE-t-2x391HC1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 5850 mm
F 2230 mm
G 6450 mm
E1 1850 mm
E2 1800 mm
H 6100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5850 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.