Skip to Content

Dry cooler BE-2x480FB1-B01T C

Dry cooler BE-2x480FB1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480FB1-B01T C

Heat rejection i
712.07 kW
Air flow
178,733 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 178,733 m³/h
External surface 3,816.9 m²
Inner volume 733.9 dm³
Fin materialAluminium
Net weight 3,535 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480FB1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
712.074 kW Fluid flow 123.50 m³/h Pressure drop 79.7 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
552.746 kW Fluid flow 95.86 m³/h Pressure drop 50.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 432.43 not rated not rated not rated not rated not rated
40 712.07 431.00 not rated not rated not rated not rated
45 984.52 707.91 429.60 not rated not rated not rated
50 1254.55 977.80 704.21 428.52 not rated not rated
55 1523.48 1245.36 971.88 701.15 427.82 not rated
60 1791.79 1511.85 1237.27 966.96 698.91 427.64

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 338.62 not rated not rated not rated not rated not rated
40 552.75 337.27 not rated not rated not rated not rated
45 760.98 549.15 336.06 not rated not rated not rated
50 967.28 755.30 545.97 335.07 not rated not rated
55 1172.68 959.58 750.31 543.36 334.40 not rated
60 1377.60 1163.00 952.83 746.18 541.44 334.17

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 712.074 123.50 79.7
Low speed (Y) 552.746 95.86 50.8

Dimensions

Dimension drawing of BE-2x480FB1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.