Skip to Content

Dry cooler BE-t-2x491GC5-C04C C

Dry cooler BE-t-2x491GC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x491GC5-C04C C

Heat rejection i
712.49 kW
Air flow
202,892 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 202,892 m³/h
External surface 1,432.4 m²
Inner volume 241.5 dm³
Fin materialAluminium
Net weight 2,157 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.8 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-t-2x491GC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
712.493 kW Fluid flow 123.65 m³/h Pressure drop 70.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
553.109 kW Fluid flow 95.93 m³/h Pressure drop 44.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 417.52 not rated not rated not rated not rated not rated
40 712.49 418.72 not rated not rated not rated not rated
45 999.63 711.56 419.78 not rated not rated not rated
50 1284.16 996.73 710.85 420.90 not rated not rated
55 1567.55 1279.54 994.44 710.56 422.13 not rated
60 1850.23 1561.15 1275.73 992.93 710.74 423.69

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 327.65 not rated not rated not rated not rated not rated
40 553.11 328.59 not rated not rated not rated not rated
45 771.89 552.28 329.42 not rated not rated not rated
50 988.41 769.58 551.72 330.32 not rated not rated
55 1203.89 984.72 767.79 551.54 331.41 not rated
60 1418.78 1198.86 981.80 766.72 551.93 332.71

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 712.493 123.65 70.5
Low speed (Y) 553.109 95.93 44.9

Dimensions

Dimension drawing of BE-t-2x491GC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 5250 mm
F 2230 mm
G 5850 mm
E1 1250 mm
E2 2400 mm
H 5500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5250 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.