Skip to Content

Dry cooler BE-2x480FD1-B01T C

Dry cooler BE-2x480FD1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480FD1-B01T C

Heat rejection i
805.46 kW
Air flow
174,875 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 174,875 m³/h
External surface 6,360.5 m²
Inner volume 1,157.0 dm³
Fin materialAluminium
Net weight 4,377 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480FD1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
805.464 kW Fluid flow 139.71 m³/h Pressure drop 46.3 kPa
Heat rejection · Low speed (Y)
606.413 kW Fluid flow 105.18 m³/h Pressure drop 27.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 504.46 not rated not rated not rated not rated not rated
40 805.46 501.59 not rated not rated not rated not rated
45 1097.40 798.90 499.02 not rated not rated not rated
50 1386.48 1087.51 793.15 496.95 not rated not rated
55 1674.26 1373.39 1078.87 788.40 495.48 not rated
60 1961.36 1658.04 1361.97 1071.74 784.92 494.85

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 383.46 not rated not rated not rated not rated not rated
40 606.41 381.08 not rated not rated not rated not rated
45 822.66 601.19 378.78 not rated not rated not rated
50 1036.84 814.92 596.33 377.05 not rated not rated
55 1250.12 1026.69 807.77 592.59 375.85 not rated
60 1462.91 1237.60 1017.34 802.25 589.87 375.33

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 805.464 139.71 46.3
Low speed (Y) 606.413 105.18 27.8

Dimensions

Dimension drawing of BE-2x480FD1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.