Dry cooler BE-2x491CB1-C04C C

Dry cooler BE-2x491CB1-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x491CB1-C04C C

Heat rejection i
804.99 kW
Air flow
235,540 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: C — generation C
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): C — C: container delivery version

Data

Coil
Air flow 235,540 m³/h
External surface 3,315.8 m²
Inner volume 415.0 dm³
Fin materialAluminium
Net weight 3,108 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x491CB1-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
804.991 kW Fluid flow 139.71 m³/h Pressure drop 129.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
646.376 kW Fluid flow 112.19 m³/h Pressure drop 87.5 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 477.46 not rated not rated not rated not rated not rated
40 804.99 477.13 not rated not rated not rated not rated
45 1124.96 802.12 476.80 not rated not rated not rated
50 1442.41 1119.69 799.62 476.63 not rated not rated
55 1758.63 1434.74 1115.08 797.56 476.67 not rated
60 2074.29 1748.78 1428.12 1111.24 796.20 477.09

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 386.60 not rated not rated not rated not rated not rated
40 646.38 386.09 not rated not rated not rated not rated
45 899.56 643.56 385.64 not rated not rated not rated
50 1150.66 894.77 641.16 385.29 not rated not rated
55 1400.77 1143.87 890.57 639.25 385.22 not rated
60 1650.32 1392.01 1137.93 887.16 637.93 385.50

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 804.991 139.71 129.2
Low speed (Y) 646.376 112.19 87.5

Dimensions

Dimension drawing of BE-2x491CB1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10050 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.