Skip to Content

Dry cooler BE-2x480FD5-B01T C

Dry cooler BE-2x480FD5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480FD5-B01T C

Heat rejection i
780.73 kW
Air flow
175,836 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 175,836 m³/h
External surface 5,387.8 m²
Inner volume 1,157.0 dm³
Fin materialAluminium
Net weight 4,207 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480FD5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
780.725 kW Fluid flow 135.42 m³/h Pressure drop 43.8 kPa
Heat rejection · Low speed (Y)
592.811 kW Fluid flow 102.82 m³/h Pressure drop 26.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 484.06 not rated not rated not rated not rated not rated
40 780.73 481.69 not rated not rated not rated not rated
45 1068.69 774.94 479.57 not rated not rated not rated
50 1353.87 1059.79 769.84 477.82 not rated not rated
55 1637.77 1341.96 1051.99 765.65 476.66 not rated
60 1920.98 1622.91 1331.55 1045.55 762.57 476.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 371.07 not rated not rated not rated not rated not rated
40 592.81 369.06 not rated not rated not rated not rated
45 807.89 588.10 367.26 not rated not rated not rated
50 1020.87 800.76 583.97 365.79 not rated not rated
55 1232.90 1011.42 794.54 580.58 364.80 not rated
60 1444.42 1221.18 1003.19 789.43 578.11 364.39

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 780.725 135.42 43.8
Low speed (Y) 592.811 102.82 26.7

Dimensions

Dimension drawing of BE-2x480FD5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.