Skip to Content

Dry cooler BE-t-2x491GC5-B04T C

Dry cooler BE-t-2x491GC5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x491GC5-B04T C

Heat rejection i
782.75 kW
Air flow
213,678 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 213,678 m³/h
External surface 1,750.9 m²
Inner volume 292.6 dm³
Fin materialAluminium
Net weight 2,426 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.1 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-t-2x491GC5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
782.746 kW Fluid flow 135.85 m³/h Pressure drop 61.3 kPa
Heat rejection · Low speed (Y)
610.829 kW Fluid flow 105.94 m³/h Pressure drop 39.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 460.99 not rated not rated not rated not rated not rated
40 782.75 461.94 not rated not rated not rated not rated
45 1095.36 780.85 462.72 not rated not rated not rated
50 1405.05 1091.19 779.37 463.57 not rated not rated
55 1713.34 1398.62 1087.67 778.38 464.57 not rated
60 2020.85 1704.72 1393.19 1085.09 778.07 465.97

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 363.54 not rated not rated not rated not rated not rated
40 610.83 364.24 not rated not rated not rated not rated
45 850.38 609.30 364.86 not rated not rated not rated
50 1087.36 846.98 608.06 365.43 not rated not rated
55 1323.13 1082.19 844.17 607.29 366.31 not rated
60 1558.24 1316.25 1077.91 842.19 607.18 367.55

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 782.746 135.85 61.3
Low speed (Y) 610.829 105.94 39.3

Dimensions

Dimension drawing of BE-t-2x491GC5-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 5250 mm
F 2330 mm
G 5850 mm
E1 1250 mm
E2 2400 mm
H 5500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5850 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.