BE-t-2x391HB1-C04C C
610.89 kW
Defrost: None
Product code: BE-2x491BB1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 223,028 m³/h |
|---|---|
| External surface | 1,550.2 m² |
| Inner volume | 243.1 dm³ |
| Fin material | Aluminium |
| Net weight | 2,315 kg |
| Quantity | 8 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 22,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x491BB1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 351.33 | not rated | not rated | not rated | not rated | not rated |
| 40 | 610.87 | 352.71 | not rated | not rated | not rated | not rated |
| 45 | 864.97 | 610.66 | 353.85 | not rated | not rated | not rated |
| 50 | 1117.25 | 863.31 | 610.46 | 354.92 | not rated | not rated |
| 55 | 1368.74 | 1114.25 | 861.91 | 610.46 | 356.03 | not rated |
| 60 | 1619.81 | 1364.47 | 1111.70 | 860.95 | 610.80 | 357.27 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 286.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 494.38 | 287.21 | not rated | not rated | not rated | not rated |
| 45 | 697.68 | 494.05 | 288.14 | not rated | not rated | not rated |
| 50 | 899.42 | 696.16 | 493.80 | 288.99 | not rated | not rated |
| 55 | 1100.42 | 896.76 | 694.91 | 493.75 | 289.88 | not rated |
| 60 | 1301.04 | 1096.68 | 894.52 | 694.03 | 493.98 | 290.91 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 610.868 | 106.01 | 73.8 |
| Low speed (Y) | 494.381 | 85.80 | 50.8 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 5250 mm |
| F | 2330 mm |
| G | 5850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 5500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |