BE-2x480CB5-B01C C
613.83 kW
Defrost: None
Product code: BE-t-2x480GC1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 152,271 m³/h |
|---|---|
| External surface | 1,599.3 m² |
| Inner volume | 234.9 dm³ |
| Fin material | Aluminium |
| Net weight | 2,080 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.1 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x480GC1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 364.47 | not rated | not rated | not rated | not rated | not rated |
| 40 | 613.11 | 365.38 | not rated | not rated | not rated | not rated |
| 45 | 853.59 | 611.75 | 366.03 | not rated | not rated | not rated |
| 50 | 1091.30 | 850.34 | 610.61 | 366.77 | not rated | not rated |
| 55 | 1327.72 | 1086.27 | 847.59 | 609.85 | 367.73 | not rated |
| 60 | 1563.40 | 1320.97 | 1082.02 | 845.51 | 609.74 | 369.07 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 280.03 | not rated | not rated | not rated | not rated | not rated |
| 40 | 465.50 | 280.49 | not rated | not rated | not rated | not rated |
| 45 | 644.06 | 464.01 | 280.89 | not rated | not rated | not rated |
| 50 | 820.35 | 640.98 | 462.80 | 281.36 | not rated | not rated |
| 55 | 995.58 | 815.80 | 638.46 | 462.03 | 282.05 | not rated |
| 60 | 1170.23 | 989.63 | 812.07 | 636.69 | 461.86 | 283.06 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 613.109 | 106.33 | 47.6 |
| Low speed (Y) | 465.500 | 80.74 | 29.2 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 4850 mm |
| F | 2230 mm |
| G | 5450 mm |
| E1 | 1150 mm |
| E2 | 2200 mm |
| H | 5100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.