Skip to Content

Dry cooler BE-2x491FC5-C04C C

Dry cooler BE-2x491FC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x491FC5-C04C C

Heat rejection i
863.82 kW
Air flow
229,724 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 229,724 m³/h
External surface 3,554.0 m²
Inner volume 822.6 dm³
Fin materialAluminium
Net weight 3,462 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x491FC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
863.820 kW Fluid flow 149.82 m³/h Pressure drop 32.5 kPa
Heat rejection · Low speed (Y)
680.249 kW Fluid flow 117.98 m³/h Pressure drop 21.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 514.00 not rated not rated not rated not rated not rated
40 863.82 513.97 not rated not rated not rated not rated
45 1204.13 860.55 513.83 not rated not rated not rated
50 1541.24 1197.94 857.65 513.84 not rated not rated
55 1876.88 1532.30 1192.57 855.40 514.13 not rated
60 2211.69 1865.21 1524.49 1188.23 853.96 514.88

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 408.39 not rated not rated not rated not rated not rated
40 680.25 408.12 not rated not rated not rated not rated
45 944.03 677.25 407.87 not rated not rated not rated
50 1205.12 938.62 674.62 407.71 not rated not rated
55 1464.96 1197.40 933.91 672.55 407.83 not rated
60 1724.11 1454.99 1190.70 930.14 671.24 408.39

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 863.820 149.82 32.5
Low speed (Y) 680.249 117.98 21.2

Dimensions

Dimension drawing of BE-2x491FC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10050 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.