Dry cooler BE-2x691EB5-C04C C

Dry cooler BE-2x691EB5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x691EB5-C04C C

Heat rejection i
864.30 kW
Air flow
314,394 m³/h
Fans
12 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 314,394 m³/h
External surface 1,999.1 m²
Inner volume 474.0 dm³
Fin materialAluminium
Net weight 3,310 kg
Fans
Quantity 12
Diameter 910 mm
Speed 840 rpm
Power 33,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 69.0 dB(A)
Sound power 101.4 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x691EB5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
864.296 kW Fluid flow 150.02 m³/h Pressure drop 119.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
692.954 kW Fluid flow 120.26 m³/h Pressure drop 80.3 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 502.25 not rated not rated not rated not rated not rated
40 864.30 503.57 not rated not rated not rated not rated
45 1219.36 863.92 504.77 not rated not rated not rated
50 1572.13 1217.40 863.71 505.96 not rated not rated
55 1923.86 1568.63 1215.87 863.83 507.33 not rated
60 2275.04 1918.90 1565.82 1214.97 864.45 508.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 405.77 not rated not rated not rated not rated not rated
40 692.95 406.81 not rated not rated not rated not rated
45 974.05 692.64 407.78 not rated not rated not rated
50 1253.16 972.45 692.48 408.80 not rated not rated
55 1531.33 1250.29 971.25 692.66 409.98 not rated
60 1809.00 1527.28 1248.09 970.66 693.34 411.46

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 864.296 150.02 119.0
Low speed (Y) 692.954 120.26 80.3

Dimensions

Dimension drawing of BE-2x691EB5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 7650 mm
F 2230 mm
G 8250 mm
E1 1250 mm
E2 1200 mm
E3 2400 mm
H 7900 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.