Skip to Content

Dry cooler BE-2x580AB1-B01T C

Dry cooler BE-2x580AB1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x580AB1-B01T C

Heat rejection i
673.27 kW
Air flow
212,535 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 212,535 m³/h
External surface 2,513.6 m²
Inner volume 348.8 dm³
Fin materialAluminium
Net weight 2,907 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 90.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x580AB1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
673.265 kW Fluid flow 116.86 m³/h Pressure drop 45.9 kPa
Heat rejection · Low speed (Y)
536.538 kW Fluid flow 93.12 m³/h Pressure drop 30.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 388.85 not rated not rated not rated not rated not rated
40 673.27 390.18 not rated not rated not rated not rated
45 950.73 672.37 391.24 not rated not rated not rated
50 1225.96 947.88 671.55 392.22 not rated not rated
55 1500.11 1221.24 945.37 671.00 393.26 not rated
60 1773.70 1493.60 1217.10 943.47 670.92 394.53

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 312.66 not rated not rated not rated not rated not rated
40 536.54 313.59 not rated not rated not rated not rated
45 754.26 535.51 314.33 not rated not rated not rated
50 969.88 751.49 534.65 315.04 not rated not rated
55 1184.65 965.62 749.21 534.04 315.86 not rated
60 1398.91 1178.85 961.96 747.42 533.79 316.84

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 673.265 116.86 45.9
Low speed (Y) 536.538 93.12 30.6

Dimensions

Dimension drawing of BE-2x580AB1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 6450 mm
F 2330 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7050 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.