BE-2x391CC5-B04T C
675.78 kW
Defrost: None
Product code: BE-t-2x480GC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 159,700 m³/h |
|---|---|
| External surface | 1,894.5 m² |
| Inner volume | 275.5 dm³ |
| Fin material | Aluminium |
| Net weight | 2,345 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x480GC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 411.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 674.99 | 410.47 | not rated | not rated | not rated | not rated |
| 45 | 930.96 | 671.85 | 409.94 | not rated | not rated | not rated |
| 50 | 1184.31 | 925.59 | 669.22 | 409.62 | not rated | not rated |
| 55 | 1436.43 | 1176.81 | 921.06 | 667.24 | 409.69 | not rated |
| 60 | 1687.89 | 1426.85 | 1170.46 | 917.58 | 666.13 | 410.19 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 314.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 510.21 | 313.83 | not rated | not rated | not rated | not rated |
| 45 | 699.64 | 507.56 | 313.26 | not rated | not rated | not rated |
| 50 | 887.04 | 695.26 | 505.34 | 312.94 | not rated | not rated |
| 55 | 1073.50 | 881.02 | 691.59 | 503.70 | 312.94 | not rated |
| 60 | 1259.45 | 1065.88 | 875.97 | 688.81 | 502.79 | 313.41 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 674.986 | 117.05 | 121.4 |
| Low speed (Y) | 510.214 | 88.50 | 74.0 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 4850 mm |
| F | 2330 mm |
| G | 5450 mm |
| E1 | 1150 mm |
| E2 | 2200 mm |
| H | 5100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.