Skip to Content

Dry cooler BE-t-2x480GC1-B01T C

Dry cooler BE-t-2x480GC1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x480GC1-B01T C

Heat rejection i
674.99 kW
Air flow
159,700 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 159,700 m³/h
External surface 1,894.5 m²
Inner volume 275.5 dm³
Fin materialAluminium
Net weight 2,345 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-t-2x480GC1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
674.986 kW Fluid flow 117.05 m³/h Pressure drop 121.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
510.214 kW Fluid flow 88.50 m³/h Pressure drop 74.0 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 411.15 not rated not rated not rated not rated not rated
40 674.99 410.47 not rated not rated not rated not rated
45 930.96 671.85 409.94 not rated not rated not rated
50 1184.31 925.59 669.22 409.62 not rated not rated
55 1436.43 1176.81 921.06 667.24 409.69 not rated
60 1687.89 1426.85 1170.46 917.58 666.13 410.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 314.52 not rated not rated not rated not rated not rated
40 510.21 313.83 not rated not rated not rated not rated
45 699.64 507.56 313.26 not rated not rated not rated
50 887.04 695.26 505.34 312.94 not rated not rated
55 1073.50 881.02 691.59 503.70 312.94 not rated
60 1259.45 1065.88 875.97 688.81 502.79 313.41

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 674.986 117.05 121.4
Low speed (Y) 510.214 88.50 74.0

Dimensions

Dimension drawing of BE-t-2x480GC1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 4850 mm
F 2330 mm
G 5450 mm
E1 1150 mm
E2 2200 mm
H 5100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5450 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.