BE-980ED5-B01 C
746.60 kW
Defrost: None
Product code: BE-2x580EC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 203,836 m³/h |
|---|---|
| External surface | 2,694.4 m² |
| Inner volume | 627.1 dm³ |
| Fin material | Aluminium |
| Net weight | 3,172 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x580EC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 446.61 | not rated | not rated | not rated | not rated | not rated |
| 40 | 747.30 | 446.41 | not rated | not rated | not rated | not rated |
| 45 | 1040.48 | 744.74 | 446.27 | not rated | not rated | not rated |
| 50 | 1331.24 | 1035.90 | 742.65 | 446.26 | not rated | not rated |
| 55 | 1620.87 | 1324.62 | 1032.00 | 741.11 | 446.57 | not rated |
| 60 | 1909.85 | 1612.24 | 1318.98 | 1029.00 | 740.28 | 447.31 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 349.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 578.51 | 348.84 | not rated | not rated | not rated | not rated |
| 45 | 801.82 | 576.41 | 348.64 | not rated | not rated | not rated |
| 50 | 1023.07 | 798.04 | 574.66 | 348.54 | not rated | not rated |
| 55 | 1243.38 | 1017.69 | 794.89 | 573.41 | 348.78 | not rated |
| 60 | 1463.17 | 1236.42 | 1013.17 | 792.52 | 572.81 | 349.43 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 747.300 | 129.69 | 74.9 |
| Low speed (Y) | 578.512 | 100.34 | 47.4 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 6450 mm |
| F | 2330 mm |
| G | 7050 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7050 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.